BI COMB SGM AC/ASL/ASH

WATER TUBES BOILER, FOR SOLID FUELS

BI COMB SGM AC/ASL/ASH

-AC version 8 bars max. operating temp. 95°C.

-ASL version 5 bars - max. operating temp. 145°C.

-ASH version 12 bars - operating temp. 175°C.

-ASH version 15 bars - operating temp. 185°C.

-Water-tube boiler designed specifically for solidfuels, with tube structure shaped to meet the specific requirements of easy cleaning and correct combustion Suitable for correct combustion of biomass (aslisted below), in compliance with current emission standards.Range consisting of 9 models with useful heat outputs from 930 kW to 5,815 kW, featuring ON - OFF operation and the possibility to be calibrated below rated output.

-Mechanical furnace screw feed, designed together with the boiler.

-Two-stage combustion, with grate-level gasification and a wide range of primary air/secondary air ratios according to the type of fuel used. Secondary air injected by independent high-turbulence system.

-Very wide and high combustion chamber, partially cooled, for the correct duration of the hot flue gas at temperatures varying between 1,100 and 1,300°C, depending on the fuel used.

-Upper post-combustion chamber, with high turbulence, thanks to the special secondary air injection system.

-High-quality mixed cast and brick refractory cladding according to the zone (AL2O3>62%), with the possibility of specific refractory cladding for special fuels.

-Tube bundle and shape of flue gas path guarantees minimum cleaning operations and complete accessibility and complete access, with efficiency exceeding 90%.

-Reduced specific heat loads at the furnace.

-Completely tubular structure.

-Lower water content, therefore less thermal inertia and greater rapidity in reaching steady operating conditions.

-Less dangerous in the event of leaks or explosions.